Static Pressure Calculator
November 12, 2026
| # | Duct | Length | Airflow | Velocity | Ends In | C | Friction Rate | Straight Loss | Fitting Loss | Section Loss |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | — in round | — | — | — | no fitting | — | — | — | — | — |
Total Straight Duct— ft
Straight Duct Loss— in. w.c.
Fitting Loss— in. w.c.
Static Pressure— in. w.c.
Length in feet, airflow in CFM, velocity in FPM, friction rate in inches of water column
per 100 ft, and every loss in inches of water column, all at standard air. Straight duct is
charged at the friction loss rate for the section's airflow and size (rectangular duct by its equivalent round
diameter; flexible duct at the flexible-duct rate raised for its compression). Each fitting
is its SMACNA loss coefficient C times the velocity pressure of the section feeding it (for a
contraction, the smaller section leaving it), Vp = (V ÷ 4005)²; a diffuser is
charged from its performance data.