About this calculator This calculator determines the valve Kv coefficient needed for a given flow rate and allowable pressure drop. Kv represents the flow in cubic meters per hour of water at a 1-bar pressure drop. Use it when selecting control valves to ensure the valve provides the required flow capacity at the design pressure drop for the hydronic circuit.
Use when You need to determine the required valve Kv for a known flow and pressure drop.
Formula Kv = Q × √(SG ÷ ΔP)
Variables
Units Metric (m³/h, bar) or Imperial (GPM, PSI)Flow Rate Flow rate in m³/h or GPMΔP Pressure drop in bar or PSI
Metric (m³/h, bar)
Units
Measurement system for flow and pressure
Flow Rate (m³/h)
Design flow rate through the valve
Pressure Drop (bar)
Allowable pressure drop across the valve

Required Kv
Recommended Kvs (×1.3)

What is valve Kv?

Kv is the flow coefficient used internationally to express a valve's flow capacity. It is defined as the flow rate in cubic meters per hour (m³/h) of water at 5–40°C that produces a pressure drop of 1 bar across the valve. Kv is calculated from the relationship: Kv = Q × √(SG ÷ ΔP), where Q is the flow rate in m³/h, SG is the specific gravity of the fluid relative to water, and ΔP is the pressure drop in bar. A higher Kv indicates a larger valve or more open flow path. When selecting control valves for hydronic HVAC systems, the design Kv should typically allow the valve to operate between 50% and 80% open at design conditions, leaving travel available for control above and below the design point. Valve authority (the ratio of valve pressure drop to total circuit pressure drop) should be at least 0.3–0.5 for stable control.