About this calculator
This calculator determines the outdoor air heating and cooling loads for a selected location in a single pass. It uses an explicit indoor Space RH value to compute latent loads accurately — the cooling setpoint and space humidity together define the indoor humidity ratio that outdoor air is conditioned to. When a weather station is selected, ASHRAE 99.6% heating and 0.4% cooling design conditions autofill automatically. Optional dehumidification and enthalpy design conditions enable a side-by-side comparison showing how the cooling coil load changes across the three ASHRAE summer design scenarios — essential for sizing equipment in humid climates where peak latent conditions occur on cooler days than the cooling-design peak.
Use when You need to size ventilation air loads for winter heating and summer cooling, or compare how different ASHRAE summer design conditions affect cooling coil sizing.
Variables
CFM Outdoor air volume in CFMHeating Setpoint Indoor heating design temperature °FCooling Setpoint Indoor cooling design temperature °FSpace RH Typical indoor relative humidity at the cooling setpoint — drives the latent calculationOutdoor Design Conditions Barometric pressure, winter dry bulb, summer dry bulb and wet bulb, and the optional dehumidification and enthalpy conditions — autofilled from the selected weather station or entered by hand
CFM
Outdoor air volume flow rate
Heating Setpoint (°F)
Indoor heating design temperature
Cooling Setpoint (°F)
Indoor cooling design temperature
Space RH (%)
Typical indoor relative humidity at the cooling setpoint
Outdoor Design Conditions
Select a weather station to autofill outdoor design conditions.

Enter CFM and outdoor conditions to see loads.

What is outdoor air load?

Outdoor air load is the heating or cooling energy required to condition ventilation air from outdoor conditions to the desired indoor conditions. It has both sensible and latent components. The sensible outdoor air load is calculated as: Sensible Load (BTU/hr) = 1.08 × CFM × (T_outdoor − T_indoor). The latent outdoor air load is: Latent Load (BTU/hr) = 0.69 × CFM × (W_outdoor − W_indoor) when W is in grains per pound, or 4840 × CFM × ΔW when W is in lb/lb. Both loads are multiplied by a density factor for the site's barometric pressure, so they drop at altitude. The outdoor air fraction required by ASHRAE Standard 62.1 for acceptable indoor air quality is the primary driver of this load. Energy recovery ventilators (ERVs) and demand-controlled ventilation (DCV) are the two most common strategies for reducing outdoor air load in commercial buildings. ASHRAE publishes three summer design conditions for each weather station: the cooling condition (0.4% dry bulb with mean coincident wet bulb), the dehumidification condition (0.4% dew point with mean coincident dry bulb), and the enthalpy condition (0.4% total enthalpy with mean coincident dry bulb). Each is exceeded only 0.4% of the year, about 35 hours, and they are independent statistics — the cooling condition is the hottest, the dehumidification condition is often cooler and much more humid, and the enthalpy condition has the highest total heat content. In humid climates, the dehumidification or enthalpy condition can produce a larger total cooling coil load than the cooling design condition, because the latent portion grows faster than the sensible portion shrinks. Comparing all three prevents undersizing for latent-dominated conditions.