About this calculator This calculator determines the outdoor air heating and cooling loads for a selected location in a single pass. It uses an explicit indoor Space RH value to compute latent loads accurately — the cooling setpoint and space humidity together define the indoor humidity ratio that outdoor air is conditioned to. When a weather station is selected, ASHRAE 99.6% heating and 0.4% cooling design conditions autofill automatically. Optional dehumidification and enthalpy design days enable a side-by-side comparison showing how the cooling coil load changes across the three ASHRAE summer design scenarios — essential for sizing equipment in humid climates where peak latent conditions occur on cooler days than the cooling-design peak.
Use when You need to size ventilation air loads for winter heating and summer cooling, or compare how different ASHRAE summer design conditions affect cooling coil sizing.
Variables
CFM Outdoor air volume in CFMHeating Setpoint Indoor heating design temperature °FCooling Setpoint Indoor cooling design temperature °FSpace RH Typical indoor relative humidity at the cooling setpoint — drives the latent calculation
CFM
Outdoor air volume flow rate
Heating Setpoint (°F)
Indoor heating design temperature
Cooling Setpoint (°F)
Indoor cooling design temperature
Space RH (%)
Typical indoor relative humidity at the cooling setpoint
Outdoor Design Conditions
Select a weather station to autofill outdoor design conditions.

Enter CFM and outdoor conditions to see loads.

What is outdoor air load?

Outdoor air load is the heating or cooling energy required to condition ventilation air from outdoor conditions to the desired indoor conditions. It has both sensible and latent components. The sensible outdoor air load is calculated as: Sensible Load (BTU/hr) = 1.08 × CFM × (T_outdoor − T_indoor). The latent outdoor air load is: Latent Load (BTU/hr) = 0.68 × CFM × (W_outdoor − W_indoor) when W is in grains per pound, or 4840 × CFM × ΔW when W is in lb/lb. The outdoor air fraction required by ASHRAE Standard 62.1 for acceptable indoor air quality is the primary driver of this load. Energy recovery ventilators (ERVs) and demand-controlled ventilation (DCV) are the two most common strategies for reducing outdoor air load in commercial buildings. ASHRAE publishes three summer design conditions for each weather station: the cooling design day (peak dry bulb with mean coincident wet bulb), the dehumidification design day (peak dewpoint with mean coincident dry bulb), and the enthalpy design day (peak total enthalpy with mean coincident dry bulb). These are three independent statistical peaks — the cooling day is the hottest hour of the year, the dehumidification day is often cooler and much more humid, and the enthalpy day captures the hour with maximum total heat content. In humid climates, the dehumidification or enthalpy condition can produce a larger total cooling coil load than the cooling design day, because the latent portion grows faster than the sensible portion shrinks. Comparing all three prevents undersizing for latent-dominated conditions.